Ground for 400 amp service. Ground size for 30, 40, and 50 amp breaker. Well, it is mandatory t...

The size of the ground rod for a 400 amp service is c

I disagree with the need for 1/0 for the grounding electrode conductor. This is one of those strange anomalies in the code. If you have a 400 amp meter main then 1/0 is needed for the grounding electrode conductor however, if you have 2- 200 amp disconnects with 3/0 copper to each then a #2 is all that is required to the ground electrode.You need to be careful when sizing the conductor from the main system bonding point (service neutral/ground connection) to the acceptable grounding …The green colored insulated conductor of the feeder must be connected to the grounding bar inside the main electrical distribution panel and to the grounding bus inside the service entrance equipment located on or adjacent to the manufactured dwelling. ... Amp max. All Locations not specified below 24 in. 6 in. 18 in. 12 in.How Much Does A 800-Amp Service Cost? If you want to install two 400A services, each 400A service could cost you as much as $4,000. On the other hand, you may spend an estimated $750 to $2,000 on each 200A service. 800-Amp Service Installation Cost. You may spend $10,000 or more depending on the kind of setup you have in mind.electric service requirements 500.0 revision page 11/15/2022 table of contents b paragraph pageUpgrading electrical service involves installing a new 200 amp distribution panel, meter socket, and electrical wiring. The cost to upgrade a breaker panel or electric service will vary depending on your location and the work needed, but it typically costs between $1,630 and $4,070. The National average is $2,730.NEC Section 230.71 has undergone a significant overhaul for the 2020 Code cycle, namely, the omission of the previous permission to install six switches or sets of circuit breakers acting as service disconnect, in a single enclosure. You are still allowed four, five, or even six switches or circuit breakers to act as the one service disconnect ...Overview. The Square D 400 Amp 30-Space 40-Circuit Combination Meter Socket and Dual Main Breaker Load Center is suitable for use as a combination service entrance device (CSED) and is a ring-type unit. It is suitable for underground service applications. Accommodates plug-on secondary surge arrestor, and features a plug-in design for easy ...Sep 30, 2004. #7. Re: 400 amp service Since each of these panels is service equipment, each has a "grounded service conductor" and also has the grounded/grounding bus bonded to the service enclosure. Per 250.53 (D) (2), you can bond at any of these locations: "The supplemental electrode shall be permitted to be bonded to the grounding electrode ...Tyler, Texas USA. Dec 31, 2018. #1. I am contractor on building my own home. I had electrician install a 400 amp service that goes from meter base/shutoff to house that has 2 200 panels. The shutoff at meter base has 2 ground rods 5-6ft apart and 2 ground rods at house panels 5-6ft as well. The bonding strap to neutral is hooked up in panels is ...phase 240 150ft from house do to power company and tree issues. He ran 2 runs of Wesleyan cable I believe 350/350/4/ to the 2-200 amp panels at house underground service.There are 2 ground rods at safety switch 5ft apart and tied into neutral there and also 2 ground rods at house for 2 200 amp panels.Building my 1st 400 Amp service tomorrow! here's my set up: 400 A Milbank Meter / underground fed 3 Double Lugs on secondary side Using 4/0 AL to (2) ... Minimum #6 copper to ground rods... Or #1/0 copper as infinity said to a water pipe electrode... shortcircuit2 . davedottcom Senior Member. Jun 19, 2005 #4That said, a 400-amp service will give you a lot more flexibility. You can have two good sized 200 amp panels in different parts of the house, Each panel will hold around 40 breakers. This allows more runs, and shorter runs from the panels to the outlets and other devices. Shorter runs mean less voltage drop that means less heat generated in ...45 posts · Joined 2012. #1 · Jan 9, 2022. I am doing a 400a residential service with 2-200a panels. There is no incoming water main, it's on a well with poly and no ufer. It's under 2020 code so I'm setting two 200a emergency disconnects outside which will also serve as the service disconnects. Since there is no other means to ground ...4 AWG copper ground wire for 200 amp service (at short distances). 0 AWG aluminum ground wire for 200 amp service (at short distances). Now, this is relevant is the hot wire is short. If you need a 200 amp service 50 feet, 100 feet, 150 feet, or 200 feet away (Example: 200 amp sub-panel 100 feet away), you also need to account for voltage drop.service conductors must be bonded in accordance with the National Electrical Code. • A water line shall not be the sole means of grounding. 10. When either lightning rods or telephone ground rods are within 6 feet of the service ground, they must be bonded together with #6 stranded copper wire with approved clamps. 11.Upper Jay, NY. May 7, 2007. #3. millspgh said: I need to give a price on a 400 amp, 3 phase 4 wire service, and I don't want to get burned by the derating issue. I was planning on running 4 500mcms in a 4" pvc pipe, the pipe will be about 100' long above a drop ceiling in a retail area. I know by having 4 current carrying conductors I need to ...Removing existing 400 amp meter base and replacing with CT cabinet with meter installed on right side if CT cabinet. Planning on installing a trough above cabinet extending over the left side. Coming out of cabinet to a 600 amp service rated ATS and then over to a 600 amp exterior MDP to feed the 3- 200 amp panels.I have (2) 400 amp 3 phase panels that will supply 7 apartments each with 100 amp sub-panels. When doing the load calculations of 25,000 va each before demand factors and after using demand factors of 40 percent on total load I came up with around 388 amps. Splitting that into (2) 3 phase panels 400 amps each.10-01-18. ER 19-240-M. PAGE 2OF 7. SERVICE ENTRANCE - OVERHEAD. Single & Three Phase 100, 200, & 320/400 Amp. 1. GENERAL: 1.1 Residential electric and gas meters should bot h be located on the same side of the home within the front 1/3 to aid meter reading, testing and se rvice, and to aid emergency response in the event of a fire or some other ...Installing an in-ground basketball goal takes no time compared to the countless hours of use that goal will get. Expert Advice On Improving Your Home Videos Latest View All Guides ...At the big 400 amperes current, the voltage drop is less significant. To help you out, we have prepared 2 charts for running a 0-500 feet wire for 400 amp service at 120V and 220V voltages. The 1st one accounts for a 3% allowable voltage drop, while the 2nd one accounts for a less rigorous 10% allowable voltage drop.Total Time: 15 mins. The main electrical service delivered to your house from the electrical utility company has a total available capacity, measured in amps, or amperes. Most homes have an electrical service of between 100 to 200 amps. Amperage is a measurement of the volume of electricity flowing through wires, and this measurement can vary ...Good Morning If you have a residential home with 120/240 volts single phase 400 amp service with 2 - 200 amp panels fed off one 400 amp service meter with seperate 4/0 SER what size ground wire is ran for grounding electrodes (rods) and to water main.Detailed Description: Schneider Electric/Square D NQ Load Center grounding bar assembly features one main grounding lug that directly mounts with two terminal screws for easy installation. It is used on QO and home line load center. It features 27 terminals of size 4 AWG - 500 MCM and 4 to 3/0 AWG. It measures 4.200 Inch x 4.900 Inch x 16 Inch.If you have some furniture with dings or scuffs you'd like to disguise on the cheap, coffee grounds are an inexpensive and easy way to touch up the imperfections. If you have some ...Re: Parallel 3/0 or 4/0 for 400-amp. The required ampacity of service conductors is called for in 230.42 (A), and is based on the load calculations (125% of continuous loads plus 100% of noncontinuous loads). The ampacity of the conductors is to be determined from 310.15, which includes 310.15 (B) (2) (a). As you have stated: 6 current carrying ...Oct 1, 2023 · Do the grounding rods need to be different for a 100 amp service, for 200 amp service, and for a 400 amp service? No, they don’t. All three service panels in a residential setting will need at least 2 ground rods, except in the circumstance described above (the rod has very low resistance). When is a ground rod required?What is the minimum size of the copper grounding electrode conductor permitted to run to an 8 foot ground rod, to a 400 amp service installed with 500 kcmil copper? ... Table 250.66 Grounding Electrode Conductor for Alternating-Current Systems A feeder circuit for a 400 amp sub panel is installed in a nonmetallic raceway using 3/0 copper ...200 Amp U5168-XTL-200-KK 4. 4 JAW - 320/400 AMP: 4.1 Used for the following services: 120/240 volt, 1 phase, 3 wire 4.2 Approved Sockets: 4.2.1 Sockets shall meet all specifications in 1.10 above. 4.2.2 The right line side location of the 320 amp socket box shall be provided with a reduced jaw. 4.2.3 Meter sockets shall be supplied with a label ...We do the "400 amp service" also with 2 200 amp panels and a 320 amp meter base. I seen some run 1 #4 to both panels for the water pipe ground. I have also been told you need to run 2 #4 (1 to each panel) or 1 1/0 to both panels. They said you had to add the conductor area together (2 3/0). When I try the math I get 2 3/0=.2790x2=.4580Can I use 2/0 for 200 amp service? Yes, 2/0 is a common size for a 200-amp service, ... A neutral wire should ideally read close to zero voltage when measured with respect to ground or the earth. However, small voltage readings can occur due to load imbalances or other factors.A. AMPED Discussion starter. 110 posts · Joined 2010. #1 · Aug 23, 2014. I am going to be installing a 400 amp over head service to a commercial building that rents out storage units. I plan on using a 400 amp singe phase meter main combo to supply 2 200 amp 40 space MLO panels.We would like to show you a description here but the site won't allow us.Jan 28, 2010 · I know that the required size of the grounding electrode for a typical 200 Amp service is a #4 solid copper. Now, we are planning on a 400 Amp service and I'm not sure what size PG&E will be running in the 3" PVC service lateral conduit but the length is approx. 300' so I'm assuming a pretty large set of service conductors.Per NEC sec. 220 our load calc puts us at about 240 Amps. We also want to allow for additional capacity for future needs. After discussing the project with the POCO engineers, we opted against a 400 Amp service for two reasons: First it would require Current Transformer metering- no big deal, just additional equipment and cost.Ground an outlet: $25 to $100: ... Now, 200-amp service is common for most homes, and 400-amp service is often installed for very large homes with many electric appliances, such as swimming pool heaters and radiant floor systems. Rewire a House . The cost of rewiring a house ranges from $1,600 to $11,400.Re: Parallel Equipment grounding conductor size If this is a 150V-600V wye connected system, then 240.13 applies(it will have ground fault protection). If the ground fault is set to meet 250.122(F)(2) along with meeting the other conditions, then you can use 3/0 egc in each pipe. But why would use use 10 - 3/0 in the first place?We do the "400 amp service" also with 2 200 amp panels and a 320 amp meter base. I seen some run 1 #4 to both panels for the water pipe ground. I have also been told you need to run 2 #4 (1 to each panel) or 1 1/0 to both panels. They said you had to add the conductor area together (2 3/0). When I try the math I get 2 3/0=.2790x2=.4580I'm feeding two 200 Amp panels from a 400 Amp (320 class) meter base. I've seen the Siemens combo, but our POCO requirements mean it can't be used. They are saying to use an Eaton 324N for the meter base. Left and right of the meter base, I'll have Q2200MRBE 200 amp disconnects (to keep NEC 2020 happy).The 400-Amp service ranges from $2000-$4000. The greater the amperage, the higher the cost. This is why a 100-Amp service costs a maximum of $2,500 whereas homeowners will spend as much as $3000 to install a 150-Amp service.Information bulletin: Concrete encasement of customer service ducts inside customer-owned buildings [PDF, 1.8 MB] covers the details for connection of underground residential services, and clarifies the BC Hydro and B.C. Safety Authority requirements for concrete encasements of service ducts and the location of large 400 amp and 600 amp 120/240 ...Most areas will not allow a 320 amp meter base for a 400 amp commercial service. Also, you will not be able to downsize the service conductors as in residential. If you parallel the service conductors, the minimum size is 3/0 copper or 250 aluminum for a 400 amp commercial service.Ground Wire Size Calculator. The Ground Conductor Size Calculator will calculate the proper ground conductor size for grounding raceways and equipment based on ampere rating or setting of automatic overcurrent protection device in circuit ahead of equipment. This is based on NEC NFPA 70E Table 250.122. Search Amazon for your Electrical products ...So, a 250 kcmil wire is ideal for 200 amp. The size depends on how far you run the wires from the sub-panels to the main panels. The wire has to be at least 2 AWG thick. However, it also depends on the cable length. If you run a wire 200 feet away from the main electrical panel, use a minimum of 1-gauge copper wire.Wire Strength and Material. You'll need to consider wire strength and material when determining whether to use 2/0 AWG copper wire or 4/0 AWG aluminum or copper-clad wire. According to the NEC, these are the correct wire sizes for a 200-amp service: Service Rating (Amps) Copper (AWG) Aluminum or Copper-Clad (AWG) 100. 4.New member here. I need some guidance on setting up a new service. I have a 400 amp service from the utility to the meter base which will then feed (2) 200 amp disconnects. The utility requires the ground to be bonded in the meter. I have a #4 bare copper connected to 2 ground rods that will route into the meter base.A 100 amp service will need a minimum of 1.25 inches, schedule 40 or 80 PVC grey electric conduit. You can use a larger conduit to maintain the inner fill of 40% or less. A 1.5 or 2-inch conduit is best if running three or more electrical wires within the same electric conduit. Chapter 9, Table 5A of the 2020 NEC, #2 Aluminum-stranded insulated ...2 Answers. Sorted by: 2. YES you can use #4 Al as your ground. Your 1AWG Al is good for a 100 AMP feeder (actually 110). From NEC 250.122 this requires …Check out 250.66(A) which states that the sole connection from the service bond to the first ground rod shall not be required to be larger than 6 AWG copper or 4 AWG aluminum. Now look at 250.53(C) which requires the conductor connecting multiple ground rods to be sized in accordance with 250.66 which requires that you use table 250.66....For sizing a grounding electrode conductor (GEC) for a single service, the grounding electrode conductor is required to be sized in accordance with 250.66 and Table 250.66. That conductor is required to be a minimum size of 8 AWG copper and need not be larger than 3/0 AWG copper.400amp. I think everyone does it different. We used to add a service knob (emily knob) with a lag screw for support for drop. Then would run 2x2" EMT Conduits with 4/0-4/0-2/0 XHHW paralelled to meter. We bonded the 2-200 amp mains together and ran the grounding conductors you mentioned from one of the 200's.Catalog#: A800HCT1R. CT Cabinet, 400-800 Amp, Type 3R (for Window-Type Current Transformers) provide Type 3R protection and a factory-installed wiring buss for 400-800 Amp, 600 VAC current transformers. The assembly has a 50 k AIC rating.Some areas require a CT cabinet for 400 amp services. CT= current transformers. These devices read the current being used on larger loads. Aorund here we use the 320 amp meter base for a 400 amp service. A 200 amp is rated 160 amp continuous and 200 non continuous. A 400 amp base is the same 400 amp noncontinuous and 320 continuous.200 amp x 100% / 80% = 250 amps (to account for the 80% rule) Next, determine how long your wire run is. Add 20% for 100 feet and 10% for 50 feet. So, if your run is 150 feet, you'll need to increase the amperage of the wire by 30%. Hence: 250 amps x 1.3 = 325 amps. The conduit size should be able to carry 325 amps.The 400 ampere service electrical panel is one of the strongest panels in the world. The extra load of current can be handled by installing a 400 amp service. Today, we are going to discuss and find out about what size ground conductor and wire are needed for 400 amp service. Ground size for 400 amp serviceFor 150 amp, you will need a 1/0-size copper wir e size. For a 200 amp service, you will need a 250 kcmil-gauge copper wire size. For a 400 amp service, you will need a 600 kcmil-gauge copper wire size. For 600 amp, you will need a 1500 kcmil-gauge wir e size. We’ve got you covered if you want to buy a circuit breaker or a sub-panel.A 400 amp panel refers to an electrical panel capable of handling a maximum current of 400 amps. While primarily utilized in commercial and industrial settings, it can also be suitable for larger residential homes. Typically constructed from steel or aluminum, 400 amp panel boards incorporate multiple circuit breakers to safeguard …For the service wire, 150’ isn't quite far enough to have to worry about voltage drop. Service and feeder to a dwelling is entitled to a favorable derate at 83% of service size. So 400A x 0.83 = 332A. You need wire rated for at least 332A at 75C thermal. That works out to 600 kcmil aluminum. (340A).I had an ol' friend and 30 year electrician who is now 49% owner in a GA. company that does a lot of work in NC at distribution hubs ask me about wire size to the service. I sent him to table 310.15 and the 75 degree column. It was different that the prints had specked for the run 600MCM vs...205 posts · Joined 2010. #25 · May 21, 2012. Don't do it. A 200 and/or 400 amp panel can be run from the same transformer. The service wire is the only difference. 200 they'll probably run #2, for the 400 they'll probably run 2/0. The same 10 kva tub and up, will pump either and do it all day long for years to come.For 200-amp sub-panel In the case of underground service, a minimum of 1.5 inches of schedule 40 or 80 PVC conduit is required for copper wire or #4/0 AWG for aluminum and copper-clad wire. You will also require a 250 kcmil-gauge copper wire. Be sure to have the proper wire size of 200 amp.200 amp meter base wiring diagram400 amp service with two 200 amp disconnects...is my grounding across How to wire a 400 amp 480/277 panel correctlyWhat wire is needed for a 400 amp service between the mast and the.We do the "400 amp service" also with 2 200 amp panels and a 320 amp meter base. I seen some run 1 #4 to both panels for the water pipe ground. I have also been told you need to run 2 #4 (1 to each panel) or 1 1/0 to both panels. They said you had to add the conductor area together (2 3/0). When I try the math I get 2 3/0=.2790x2=.4580150 Amp Wire Size Calculator. Here you insert wire length, voltage, and allowable voltage drop, and the calculator will determine which gauge wire you need to facilitate 150 amp current immediately. 150 Amp Wire Gauge Charts for 3% and 10% voltage drop. We have calculated wire sizes needed for 150 amp service 50, 100, 150, 200, 300, 400, and ...For 150 amp, you will need a 1/0-size copper wir e size. For a 200 amp service, you will need a 250 kcmil-gauge copper wire size. For a 400 amp service, you will need a 600 kcmil-gauge copper wire size. For 600 amp, you will need a 1500 kcmil-gauge wir e size. We’ve got you covered if you want to buy a circuit breaker or a sub-panel.2. YES you can use #4 Al as your ground. Your 1AWG Al is good for a 100 AMP feeder (actually 110). From NEC 250.122 this requires an #8 CU or #6 Al ground wire as a minimum (or 6CU and 4 Al if you are really running a 110Amp Feeder). As a reminder, your feeder will be 4 wires, the two hots and the neutral will be #1AL (unless you've de-rated ...At the big 400 amperes current, the voltage drop is less significant. To help you out, we have prepared 2 charts for running a 0-500 feet wire for 400 amp service at 120V and 220V voltages. The 1st one accounts for a 3% allowable voltage drop, while the 2nd one accounts for a less rigorous 10% allowable voltage drop.The wiring diagram for a 400 amp meter base provides a visual representation of the electrical connections and components involved. It shows how the main electrical service conductors enter the meter base and how the power is distributed to different parts of the electrical system. The diagram typically includes labels and markings to identify ...We do the "400 amp service" also with 2 200 amp panels and a 320 amp meter base. I seen some run 1 #4 to both panels for the water pipe ground. I have also been told you need to run 2 #4 (1 to each panel) or 1 1/0 to both panels. They said you had to add the conductor area together (2 3/0). When I try the math I get 2 3/0=.2790x2=.4580The S&P 500 measures the performance of 500 large companies. Learn more about the S&P 500 and why it's so often referenced in investing. We may receive compensation fro...For 400 amp service, we can rule out the standard AWG wires. We have to use thick kcmil copper and aluminum wires. On top of that, we have to account for voltage drop for …Each meter socket will connect to separate 200-amp load centers with 2/0 cu conductors. My local permitting agency says I need 1/0 cu ground electrode conductor (for 400 amp service). I say I need #4 conductor for 200 amp service. It seems to me any ground fault would be cleared by a 200-amp main breaker, therefor sizing for 200 amps should apply.About 200-Amp Service Wire Size. The National Electrical Code mandates a maximum #2/0 AWG or #4/0 AWG copper wire coiled within a standard 1.5-inch PVC 40 or 80 conduits for underground service. When installing three inputs in the same conduit, we suggest 2 or 2.5 inches. You should use copper or aluminum-coated wires that measure at least AWG ...When you use Blade promo code BRIANF& F you and TPG will each earn $50 in Blade credits. Note as of 5pm ET on 3/27: When using credits for a Blade Contin... When you use Blade ...The size of the ground wire for a 200-amp service depends on various factors, including local electrical codes and specific installation conditions. However, as a general guideline, a copper grounding conductor of 4/0 AWG (American Wire Gauge) or an aluminum conductor of 250 kcal is often recommended. It's crucial to consult your local ...Ground Bar Kit For 400A & 600A BR Loadcntrs Eaton Loadcenter Ground Bar Kit, 2.34 In Mounting Hole Distance, Kit, 400 A, 600 A, Single- and Three-Phase, For 400A and 600A BR Loadcenters Slang Terms Suggest a New Term Categories Load Centers & Accessories - Load Center Accessories Mark as IncorrectThe ordinary code of wire to use for a 200 amps service panel is #2/0 copper wire that needs to have a conduit of 2 inches. The electric code of your country may also set the bar for utmost safety. For aluminum or copper-clad wire, there shall be a wire with a gauge of #4/0 AWG. The MCM rating would be 211.60 kcmil.Obviously, it’s not all that easy to get your hands on the new 2022 NEC guidebook. That’s why we list the wire sizes for feeders ranging from 100 amp to 400 amp services, in …#1. Hello all; Some clarification on the size of the GEC in a service to a residence with 2 150 amp main breaker panels. Is it determined by the size of the …A. AMPED Discussion starter. 110 posts · Joined 2010. #1 · Aug 23, 2014. I am going to be installing a 400 amp over head service to a commercial building that rents out storage units. I plan on using a 400 amp singe phase meter main combo to supply 2 200 amp 40 space MLO panels.Updated on February 15, 2024. According to the NEC, the wire size for 200 amp service is a 3/0 AWG copper wire or 4/0 AWG aluminum wire. You should increase wire size by 20% for every extra 100 feet run to account for voltage drop. For a 200-amp cable size spanning over 200 feet, choose a 500 kcmil copper wire or a 1000 kcmil aluminum wire.35 Amps. 24 Amps. 12 AWG. 20 Amps. 20 Amps. 25 Amps. 16 Amps. This aluminum ampacity chart is quite easy to read. Just find the AWG wire you want to know how many amps it can handle, check the ampacity, and in the last column, you will also find the max. allowable able such an AWG aluminum wire to conduct at a median 75°C temperature.Sep 18, 2014 · There may be no exception by your AHJ but the Code allows a lot of possibilities: 250.104 covers the bonding of "other metal piping systems" which would include the gas pipe. #3 would be correct for a 400 amp circuit, however, the section goes on to say the pipe only needs to be bonded using the rating of the circuit likely to energize the pipe.Ground an outlet: $25 to $100: ... Now, 200-amp service is common for most homes, and 400-amp service is often installed for very large homes with many electric appliances, such as swimming pool …service conductors must be bonded in accordance with the National Electrical Code. • A water line shall not be the sole means of grounding. 10. When either lightning rods or telephone ground rods are within 6 feet of the service ground, they must be bonded together with #6 stranded copper wire with approved clamps. 11.Here's what I'd do: -go to supplier pull 400A meter base and panel out of their boxes. -check: temp ratings, AL/CU rating, dual vs single lug. -use that info and T2 to choose wire size and parallel vs single run, keeping 12-108 in mind. BTW, a friend of mine priced a job last year based on using AL then. found he could only get a CU rated meter ...The ordinary code of wire to use for a 200 amps service panel is #2/0 copper wire that needs to have a conduit of 2 inches. The electric code of your country may also set the bar for utmost safety. For aluminum or copper-clad wire, there shall be a wire with a gauge of #4/0 AWG. The MCM rating would be 211.60 kcmil.If the largest service conductor carries 100 amps use a #8, 200 amps - #6, 400 amps - #3, 600 amps - #1, 800 amps - 1/0 and over 800 amps - 2/0 for the ground wire. <<>> Golden Valley Electric Assoc. in Alaska requires #4AWG copper wire for a ground from the breaker box to earth ground rod.3830 posts · Joined 2010. #7 · May 29, 2015. Here the neutral would be bonded to the CT cabinet and again at the service disconnect. The code permits the grounded conductor to be used for all of the bonding on the line side of the service disconnect, but some utilities do no permit you to use the neutral to bond the CT cabinet.May 8, 2012. #11. ceb58 said: If the customer is set on having 2-200 amp panels I would set a 400 amp meter/combo with an 8 space buss. Feed the house with the 2 200 amp breakers and put in a 100 amp on the buss for the garage. This will still give you 6 spaces you can feed the A/C, well pump or what ever.Oct 28, 2008 · Ok the code states you don’t need anything larger then a #6 solid grounding wire to bond to (2) grounding rods. You will need to space these 6’ apart minimum. Now from that main panel, you will run a 4 conductor cable from there to your 200amp panel in your home, and you will need to run a 4 conductor cable to your garage.The supports shall be spaced not more than 24 inches on center and shall be within 12 inches of any enclosure or termination. [250.64 (B)] Where the grounding electrode conductor or bonding jumper connected to a single or multiple rod, pipe, or plate electrode (s) or any combination thereof, as described in Section E3608.3, does not extend on .... For the example, the minimum size grounding-electrode conductor is 2 At the meter the feeders emerge in PVC out of the ground 4ft and at th Normally a 400 amp service would need 1/0 or possible #2 copper for the grounding electrode conductor but the code states there is no reason to be larger than #6 to the rods, as Jim posted. I think the reason is that an 8' rod in the soil will do no better than the equivalent of a #6 wire so they gave us a break. lol. Dangerous DIYer.But let's first look at what constitutes an equipment grounding conductor (EGC) and how it differs from the oft-misunderstood grounding electrode conductor (GEC) that connects noncurrent-carrying metal parts of the electrical service to the electrode buried in the earth. EGCs VS. GECs. Equipment Grounding Conductor (EGC): Table 250.122 Above the 800 amp breaker, the ratings hold a Amp 400 panel meter installed Meter amp 200 base 400 service replacing electrical subpanel Meter base amp 200 wiring diagram installation disconnect 200a … The ampacity of 4/0 aluminum per 310.16 is ...

Continue Reading